IMJ00503 V3E.DOC Page 27 of 40 19.02.2009
The following parameters are available for configuration (refer to GSD File):
ExtUserPrmData = 20
“Trigger Mode” for trigger mode
ExtUserPrmData = 21 “Trigger Level” for trigger level
ExtUserPrmData = 25 “Trigger Delay (31 16)” for trigger delay
ExtUserPrmData = 26 “Trigger Delay (15 0)” for trigger delay
For detection of a clock edge, the following voltage signals are required:
24 V > HIGH > 11 V
0 V < LOW < 6.5 V
Wiring connections for working with the trigger input are as follows:
Fig. 8: Wiring of trigger input
green
red
green
red
Setup
Power Supply
Control
white
brown
green
yellow
gray
orange
blue
red
black
violet
white/brown
white/black
Device
Terminal